Can I replace R22 with 407C?

Can I replace R22 with 407C?

The best replacement for R-22 Freon is usually R-407c. You should never under any circumstances add replacement refrigerant to a system that has any R22 refrigerant left in it.

Can I replace R134a with R407C?

Yes, there is an identified replacement for R134a, HFO1234yf, which GM will use. The future for R407C is uncertain. Other things to consider; R407C is a blend which requires total change replacement after 50% loss of charge; this also limits the reuse of refrigerant on site and the recycling of the used refrigerant.

How much 407C should we add to a R22 retrofit initially?

It is recommended that the system be initially charged with the retrofit refrigerant to about 80% by weight of the correct R-22 charge. Add as much as possible of the initial charge to the high pressure side of the system (compressor not running).

Can you charge 407C as a vapor?

R-407C should always be charged as a liquid. Due to its zeotropic nature, it will fractionate if charged as a vapor, causing poor system performance — and, possibly, system failure. Additionally, the refrigerant supply in the cylinder may become out of spec if discharged as a vapor.

What pressure should 407C run at?

If this is so always evaporating above zero, 4 or 5 deg celcius, R407c will have a low pressure (suction ) of about 50 psi. and a high pressure ( discharge ) of about 280 psi, which is about 55 deg celcius, cooling cycle. Standing pressure ( system not running ) will depend on surrounding temperature of outdoor unit.

Which is better R407C vs R410A?

While R-410A’s operating pressure at high ambient temperatures is inarguably higher than that of R-407C, at Super Radiator Coils, we’re able to produce UL-listed solutions that use R-410A for up to 700 PSIG, making it a completely safe and effective refrigerant for warmer climates.

Can you top up R407C?

Re: R407c top up. When R407C leaks, you can end up with a “refrigrant mix” with operating pressures similar to R410A. It is not practical to determine the remaining refrigerant and is usually best to reclaim and start again with new refrigerant.

Is R407C compatible with mineral oil?

For safe system operation it is essential to remove the mineral oil from the existing system, as R407C is not compatible with mineral oil.

Can I use 410a gauges for 407C?

Yes, gauges measure pressure and R22/R407c can be measured by the same instrument unlike R410a (with higher pressures probably needs a wider range gauge). What you should not use is the temperature scale.

Can I use R410A instead of R407C?

Can a heat pump be retrofitted with Freon 407C?

Using these retrofit guidelines, many R-22 systems can be retrofitted for use with Freon™ 407C in air conditioning, heat pump applications, and refrigeration applications to allow existing equipment to continue to operate safely and efficiently, even after R-22 is no longer available. Environmental Properties and Safety

Which is the best refrigerant for a retrofit?

Another ideal retrofit is the Opteon ™ refrigerant that offers comparable performance and safety characteristics to R-22, without requiring extensive changes to equipment.

What is the type code for the R407c valve?

The type code refers to the refrigerant for which the valve is designed (only for refrigerants with type letter): R22/R407C 1) = X R134a = N R404A/R507 = S R407C = Z 1) For R407C plants, please select valves from the dedicated R407C program